Two-way thermal release valve SYR 5067 - 3/4 with pressure reducing valve (capillary: 1,3 meter)
Regular price:
product unavailable
add to wish list
0
Description
Cooling valve
SYR 5067
Thread: 3/4 inch
Application: for boilers with capacity up to 100 kW
Maximum operating temperature : 135oC
Pressure reducing valve operating pressure:
1.2 bar (factory locked)
Maximum inlet water pressure: 16 bar
Minimum inlet water pressure: 2.3 bar
Opening temperature:
fill valve: 90oC +0/-2oC
discharge valve: 97oC +0/-2oC
Closing temperature:
fill valve: 88oC +0/-2oC
discharge valve: 94oC +0/-2oC
Capillary: 1300 mm - standard length
Weight: 1.5 kg
Thermal protection of the installation is used to protect solid fuel boilers in heating systems equipped with thermostatic valves in accordance with Polish Standard PN-EN303-5. It is particularly recommended for boilers that are not equipped with a cooling heat exchanger.
Thermal safety valve 5067 consists of the following parts: check valve, pressure reducer, thermically controlled fill valve and discharge valve, temperature sensor with capillary.
The reducing valve is connected to the water network, the outlet of the thermically controlled fill valve is connected to the boiler return line. The discharge valve is connected to the supply line and hot water from the heating system flows out, thanks to which the boiler cools down.